QDP

Introduction

Coefficient of Discharge: (open) 0.84, (closed) 0.344

The Robertson QDP is designed as a dual purpose unit which, under normal conditions, functions as an efficient Slope Mounted Natural Ventilator. Should fire conditions occur, the unit will automatically open to provide an almost unrestricted exhaust area.

Features and Benefits:

  1. Coefficient of Discharge - As determined by independent tests, is 0.344 with the lids closed, and 0.84 with the lids open.

  2. Maintenance Testing - Regular maintenance testing of all automatic smoke/heat release ventilators is a standard building code requirement. QDP Ventilators incorporate the necessary facilities to enable this testing.

  3. Remote Control Systems - Can be provided with electrical or pneumatic remote control systems with zone control.

  4. Materials - Can be supplied in a wide range of cladding materials including Versacor coated sheeting.

*QDP vents are designed to meet international building code standards.

Dimensions & Mass:

 

Unit Exhaust Opening (m2) Dimensions (mm) Mass
A B C D E F G Versacor Zincalume Aluminium
415 0.47 770 1326 365 520 150 1220 215 33 29 23
615 0.70 770 1934 365 520 150 1830 215 39 37 27
724 1.30 1295 2262 610 952 170 2134 215 133 99 54